LS Electric G100 General AC Drive is the first choice for general applications. It offers superior performance with powerful sensorless vector functionality, advanced performance and product features that meet high reliability standards. G100 drive is the optimum solution for you. Dual rating allows for a wide variety of applications for the AC drive, and its user-friendly design simplifies installation, control and maintenance.
- Dual rating study
- 4 kW / 17 A heavy duty - 150% overload / 1 minute
- 5.5 kW / 18 A normal duty - 120% overload / 1 minute
- 3 Phase Input, 3 Phase Output
- 200-240 Volts
- control modes: U / F, Slip compensation
- Sensorless vector IM
3 Phase 200 V (0.4-7.5 kW)
G100-2 | 0004 | 0008 | 0015 | 0022 | 0040 | 0055 | 0075 | ||
Engine Values | Harsh Conditions (HD) | (HP) | 0.5 | 1.0 | 2.0 | 3.0 | 5.4 | 7.5 | 10 |
(kW) | 0.4 | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 7.5 | ||
Normal Conditions (ND) | (HP) | 1.0 | 2.0 | 3.0 | 5.4 | 7.5 | 10 | 15 | |
(kW) | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 7.5 | 11 | ||
Output Values | Capacity [kVA] | Harsh Conditions (HD) | 1.0 | 1.9 | 3.0 | 4.2 | 6.5 | 9.1 | 12.2 |
Normal Conditions (ND) | 1.2 | 2.3 | 3.8 | 4.6 | 6.9 | 11.4 | 15.2 | ||
Rated Current (3-Phase Input) [A] | Harsh Conditions (HD) | 2.5 | 5.0 | 8.0 | 11.0 | 17.0 | 24.0 | 32.0 | |
Normal Conditions (ND) | 3.1 | 6.0 | 9.6 | 12.0 | 18.0 | 30.0 | 40.0 | ||
Rated Output (1-Phase Input) [A] | Harsh Conditions (HD) | 1.5 | 2.8 | 4.6 | 6.1 | 9.3 | 12.8 | 17.4 | |
Normal Conditions (ND) | 2.0 | 3.6 | 5.9 | 6.7 | 9.8 | 16.3 | 22.0 | ||
Frequency [Hz] | 0 ~ 400Hz (IM sensorless: 0 ~ 120Hz) | ||||||||
Voltage [V] | 3-Phase 200 ~ 240V | ||||||||
Input Values | Voltage [V] | 3-Phase 200 ~ 240VAC (-15% ~ + 10%) | |||||||
Frequency [Hz] | 50 ~ 60Hz (+ 5%) | ||||||||
Rated Current [A] | Harsh Conditions (HD) | 2.2 | 4.9 | 8.4 | 11.8 | 18.5 | 25.8 | 34.9 | |
Normal Conditions (ND) | 3.0 | 6.3 | 10.8 | 13.1 | 19.4 | 32.7 | 44.2 | ||
Weight [kg] | 1.04 | 1.06 | 1.36 | 1.4 | 1.89 | 3.08 | 3.21 |
PRODUCT CODE | SUITABLE INVERTER MODEL | RESISTANCE (ohm) | POWER (Watt) |
AKS-35-300-1200 | LSLV0004G100-4EOFN | 1200 | 100 |
AKS-30-300-600 | LSLV0008G100-4EOFN | 600 | 150 |
AKS-30-1000-300 | LSLV0015G100-4EOFN | 300 | 300 |
AKS-30-1000-200 | LSLV0022G100-4EOFN | 200 | 400 |
AKS-30-1000-130 | LSLV0040G100-4EOFN | 130 | 600 |
AKS-35-2000-85 | LSLV0055G100-4EOFN | 85 | 1000 |
AKS-35-2000-60 | LSLV0075G100-4EOFN | 60 | 1200 |